M3US and between Phases and Neutral for the H3USN Faults are signalled via LEDs, distinguishing the origin of the fault (one LED for the upper threshold, one LED for the lower threshold). Set the selector switch to the 3-phase network voltage Un.
The position of this selector switch is only taken into account when the unit is powered up. If the switch position changes while the unit is operating, all the LEDs flash but the product continues to work normally with the voltage selected on energisation prior to the change of position. The LEDs return to their normal state if the switch is reset to its initial position defined before the last energisation.
Crouzet Part Number | 84873224 (3 Phase Voltage Monitoring Relay With SPDT Contacts) |
Function | Undervoltage/Overvoltage between phases |
Nominal Voltage | 3 x 208 → 3 x 480 V ∿ |
Digital Outputs | 1 x C/O Relays, 250VAC/DC @ 5 Amp |
Min Breaking Current | 10mA/5VDC |
Timing Range | 0.3 → 30s (0, +10%) |
Delay on Pickup | 500ms |
Alarm Delay on Time (max) | 200ms |
Reset Time | 1500ms |
Fixed Hysteresis | 2% of Un |
Maximum Measurement Cycle Time | 150ms/True RMS Measurement |
Measurement Accuracy | 1% |
Supply Voltage Range | Same as Measurement 3 x 208 → 3 x 480 V ∿ |
Termination Style | Screw |
Weight | 170g |
Certification | CE, UL, CSA, GL, ROHS |
Factory Pack Qty | 1 |
Over Voltage Category | 3 in accordance with IEC/EN 60664-1 |
Pollution Degree | 2 in accordance with IEC/EN 61131-2 |
Protection rating | IP40 (Front), IP20 (Rear) |
Mechanical Resistance | Immunity to vibrations IEC/EN 60068-2-6, test Fc Immunity to shock IEC/EN 60068-2-27, test Ea |
Resistance to HF Interference | Immunity to radiated electrostatic fields IEC/EN 61000-4-3 Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 Immunity to shock waves IEC/EN 61000-4-5 Radio frequency in common mode IEC/EN 61000-4-6, level 3 Voltage dips and breaks (AC) IEC/EN 61000-4-11 Immunity to damped oscillatory waves IEC/EN 61000-4-12 |
Conducted and radiated emissions | Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1 (*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in a metal enclosure) |
Operating Temperature | -20 →+70 °C except CB and XB versions in VDC : -30 →+70 °C (+40 °C in a non-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22 |
Legend | |
1 | Overvoltage |
2 | Hysteresis |
3 | Undervoltage |
4 | Phases L1, L2, L3 |
5 | Relay R1 |
6 | Relay R2 |
7 | Overvoltage threshold delay |
8 | Undervoltage threshold delay |
The relay monitors its own supply voltage. It controls :
For all orders exceeding a value of 100USD shipping is offered for free.
Returns will be accepted for up to 10 days of Customer’s receipt or tracking number on unworn items. You, as a Customer, are obliged to inform us via email before you return the item.
Otherwise, standard shipping charges apply. Check out our delivery Terms & Conditions for more details.